Browser screen size: *
LDM-L2
LED Dimming Module for Level 2
Overview
In RLCM, the LDM (LED Dimming Module) can be connected up to 32 units and installed inside each LED fixture to control dimming and ON/OFF.
Program settings are configured via the IGS Touch Switch or STS.
The LDM-L2 Series is available in various types depending on the output configuration.
Program settings are configured via the IGS Touch Switch or STS.
The LDM-L2 Series is available in various types depending on the output configuration.
Feature
- Connected to CAN communication network
- 254-step dimming control
- 16 scene and group settings
- Data line via LAN cable CAT.6 4pr (RJ45)
- Maximum communication distance: 500m
- Address setting via random addressing using STS or MR BLE App
- Built-in address switch supporting up to 16 groups
- Dimming range: 1% ~ 100%
- Dimming time: programmable
- Output types: direct LED fixture connection or SMPS control (PWM / 0–10V)
Operation
- Applicable to various LED fixtures such as panel lights, downlights, and LED bars via CAN communication
- Connect LAN cable CAT.6 4pr to RJ45 port on each LDM-L2
- Use constant voltage LED drivers under 60V / 3A, max 180W
- Mount LDM near LED driver using screws or magnets
- Configure address and program via IGS Touch Switch or STS
- Up to 32 LDM units per RLCM system
- Supports individual / group / scene control
- 16 group settings
- 16 scene settings
- Fade time control
- Fade rate control
- Min / max level setting
- Occupancy sensor integration
- Illuminance sensor integration
Application
Speicfication
- LED load: 10W ~ 180W
- Environment: -10℃ ~ 55℃, 0~95% RH
- Input power: DC 10~60V
- Power consumption: 12 ~ 50W
- Communication: CAN
- Max communication distance: 500m
- Communication cable: CAT.6 4pr & RJ45
- Output power (POut): max 180W
- Output voltage (VOut): 12~60VDC (LDM-L2-n)
- Output current (IOut): max 3,000mA (LDM-L2-n)
- Dimming range: 1~100%
- LDM-pwm and LDM-010 are for SMPS PWM / 0–10V signal control
Network
Dimension
User Interface
Layout
System Diagram
Connect Diagram